forked from anviod/edgex
-
Notifications
You must be signed in to change notification settings - Fork 0
Expand file tree
/
Copy pathindex.md
More file actions
158 lines (126 loc) · 6.9 KB
/
Copy pathindex.md
File metadata and controls
158 lines (126 loc) · 6.9 KB
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
---
layout: section-index
title: 设备驱动
description: EdgeX 南向采集驱动文档 — Modbus、BACnet、OPC UA、S7、EtherNet/IP、FINS、SNMP、IEC 104、DL/T645、Mitsubishi MC、Profinet IO、KNXnet/IP
hero_eyebrow: Southbound Drivers
hero_lead: 南向采集驱动的设计文档、测试报告、优化方案与故障分析 — 覆盖 Modbus、BACnet、OPC UA、S7、EtherNet/IP、Omron FINS、SNMP、IEC 104、DL/T645、Mitsubishi MC、Profinet IO、KNXnet/IP 等工业协议。
hero_buttons:
- text: 返回首页
url: ../index.html
style: primary
- text: English
url: index_en.html
style: secondary
- text: 测试报告
url: ../testing/南向驱动测试报告.html
style: secondary
- text: 开发计划
url: ../development_plan/index.html
style: secondary
---
## 驱动支持矩阵
> 注册来源:`cmd/main.go` 空白导入 · 测试数据:2026-06-28 · `CGO_ENABLED=0`
| 协议 | 注册名 | 状态 | 读 | 写 | 扫描/发现 | 连接管理 | 单元测试 |
| :--- | :--- | :--- | :---: | :---: | :---: | :---: | :--- |
| Modbus TCP/RTU | `modbus-tcp`, `modbus-rtu`, `modbus-rtu-over-tcp` | 生产就绪 | 是 | 是 | — | 是 | 33 项,27% 覆盖 |
| **BACnet IP** | `bacnet-ip` | 生产就绪 | 是 | 是 | Scan + ScanObjects | 故障隔离 | 80+ 项,59% 覆盖 |
| **OPC UA Client** | `opc-ua` | 生产就绪 | 是 | 是 | Scan + ScanObjects | 是 | 25 项,40% 覆盖 |
| **Siemens S7** | `s7` | 生产就绪 | 是 | 是 | — | 是 | 52 项,42% 覆盖 |
| **EtherNet/IP** | `ethernet-ip` | 生产就绪 | 是 | 是 | — | 是 | 60 项,30% 覆盖 |
| **Omron FINS** | `omron-fins` | 生产就绪 | 是 | 是 | — | 是 | 12 项,31% 覆盖 |
| **SNMP v2c/v3** | `snmp` | 生产就绪 | 是 | 是 | ScanObjects | 是 | 22 项,45% 覆盖 |
| **IEC 60870-5-104** | `iec60870-5-104` | M1 已交付 | 是 | 是 单点遥控 | — | 是 | 16 项,45% 覆盖 |
| **DL/T645-2007** | `dlt645` | 生产就绪 | 是 | 是 | — | 是 | 24 项,71% 覆盖 |
| **Mitsubishi SLMP** | `mitsubishi-slmp` | 生产就绪 | 是 | 是 | — | 是 | 13 项,57% 覆盖 |
| **Profinet IO** | `profinet-io` | 生产就绪 | 是 | 是 | — | 是 | 11 项,49% 覆盖 |
| **KNXnet/IP** | `knxnet-ip` | 生产就绪 | 是 | 是 | 网关发现 | 是 | 13 项,67% 覆盖 |
### 主要配置参数
| 驱动 | 关键配置项 |
| :--- | :--- |
| Modbus | `ip`, `port`, `slaveId`, `timeout`,连接类型 TCP/RTU/RTU-over-TCP |
| BACnet | `ip`, `port`, `deviceId`,广播网口、对象实例 |
| OPC UA | `endpoint`,安全策略/模式,凭证,订阅间隔 |
| S7 | `ip`, `port`, `rack`, `slot`,PLC 型号 (200Smart/1200/1500/300/400) |
| EtherNet/IP | `ip`, `port`, `slot`,Tag 路径,连接类型 |
| Omron FINS | `plcIP`/`ip`, `plcPort`/`port`, `timeout`,源/目的节点地址,TCP/UDP |
| Mitsubishi MC | `ip`, `port`, `frame_type`, `network_no`, `station_no`, `timeout` |
| SNMP | `snmpVersion`, `targetIP`, `community` (v2c),USM 认证/加密 (v3),`maxBulkSize` |
| DLT645 | `connectionType` (serial/tcp), `port`, `ip`, `baudRate`, `timeout`, 表地址 + DI |
| Profinet IO | `local_interface`, `timeout`, `simulation`;设备级 `ip`, `port`, `slot`, `subslot`, `device_name` |
| KNXnet/IP | `ip`, `port`, `mode` (TCP/UDP),`discovery`, `discovery_timeout`, `discovery_multicast` |
| IEC 104 | `ip`, `port`, `commonAddress`,T0–T3 定时器,总召唤间隔 |
---
## 目录
### Modbus
- [Modbus 优化](MODBUS_OPTIMIZATION.html)
- [Modbus 优化最终报告](MODBUS_OPTIMIZATION_FINAL.html)
- [Modbus 优化报告](MODBUS_OPTIMIZATION_REPORT.html)
- [Modbus 心跳优化](MODBUS_HEARTBEAT_OPTIMIZATION.html)
- [Modbus 智能探测](Modbus智能探测.html)
- [边缘网关 Modbus 优化](边缘网关Modbus优化.html)
### BACnet
- [BACnet 设计说明](BACnet_设计说明.html)
- [BACnet 驱动采集测试验收清单](BACnet_Driver_Collection_Test_Acceptance_Checklist.html)
- [BACnet 故障隔离报告](BACnet_Fault_Isolation_Report.html)
- [BACnet 前端功能清单](BACnet_Frontend_UI_Functionality_Checklist.html)
- [BACnet 前端需求](BACnet_Frontend_UI_Requirements.html)
- [BACnet 多设备隔离测试计划](BACnet_Multi_Device_Isolation_Test_Plan.html)
- [BACnet 点位串流 bug](BACnet点位串流bug.html)
- [API BACnet](API_BACnet.html)
### OPC UA
- [OPC UA 设计](OPC_UA_Design.html)
- [OPC UA 服务端功能](OPC-UA_Server_Functionality.html)
- [OPC UA UI 审查](OPC_UA_UI审查.html)
### S7 协议
- [S7 协议](PLC_S7.html)
- [S7 连接生命周期系统](S7_Connection_Lifecycle.html)
### Profinet IO
- [Profinet IO 驱动](PLC_Profinet_IO.html)
### EtherNet/IP
- [EtherNet/IP 真实通信实现方案](EtherNet_IP驱动真实通信实现方案.html)
### Omron FINS
- [FINS 协议驱动](PLC_FINS.html)
### Mitsubishi MC
- [三菱 MC Protocol 驱动](PLC_MITSUBISHI.html)
### SNMP
- [SNMP 驱动说明](SNMP.html)
### DL/T 645
- [DL/T 645-2007 驱动](DLT645.html)
- [开发方案](../development_plan/drivers/DL-T-645-2007驱动开发.html)
### IEC 60870-5-104
- [ICE104 开发计划](../development_plan/drivers/采集驱动ICE104开发.html)
### 测试报告
- [南向驱动测试报告](../testing/南向驱动测试报告.html)
- [Southbound Driver Test Report (EN)](../testing/southbound-driver-test-report.html)
---
## 连接管理系统 (2026-06)
### ConnectionManager 公共组件
**核心特性**:
- 统一连接状态机:`Disconnected → Connecting → Connected → Retrying → Dead`
- 指数退避算法:`backoff = min(base_delay × 2^retry_count, max_delay) + jitter`
- 冷却期策略:基础冷却 1 分钟,指数增长,最大 1 小时
- 每日清零机制:每日零点自动重置重试计数与冷却次数
**适用驱动**: S7、Modbus、EtherNet/IP、OPC UA、FINS、SNMP、DL/T645、Profinet IO、KNXnet/IP
### 采集健康检测
> 采集成功 = 连接健康 · 采集失败 = 连接异常 · 连续失败达到阈值 → 触发状态变更
| 驱动/型号 | 最大失败次数 | 默认采集周期 | 说明 |
| :--- | :--- | :--- | :--- |
| **S7-200Smart** | 3 次 | 60 秒 | 弱 PLC,保护设备 |
| **S7-1200/1500** | 5 次 | 10 秒 | 标准 PLC |
| **Modbus** | 5 次 | 可配置 | 通用设置 |
| **EtherNet/IP** | 5 次 | 可配置 | Rockwell 系列 |
| **OPC UA** | 5 次 | 订阅回调触发 | 订阅数据质量判断 |
| **FINS** | 5 次 | 可配置 | 欧姆龙 PLC |
| **SNMP** | 5 次 | 可配置 | 网络设备 |
### 低频采集补偿探测
当采集周期超过 3 倍阈值时,自动触发轻量探测请求:
- S7:读取 M 区 1 字节
- Modbus:读取单个寄存器
- EtherNet/IP:读取单个 Tag
- OPC UA:读取 ServerStatus 节点
---
## 相关文档
- [开发计划](../development_plan/index.html) — 待开发驱动规划
- [架构设计](../architecture/index.html) — ScanEngine 与 ShadowCore
- [测试验证](../testing/index.html) — 测试方案与报告