5 changes: 3 additions & 2 deletions identified.md
Original file line number Diff line number Diff line change
Expand Up @@ -22,10 +22,11 @@ analysis.
| 38 | Internal Unit Temp | ×0.1 | °C | −2.2 – 21.8 | STATISTICAL | Tracks outdoor ambient +5°C offset; r=0.953 vs reg_39 — consistent with enclosure heat from inverter/compressor. AP mode label: "T3 Suction" |
| 39 | Outdoor Ambient Temp | ×0.1 | °C | −5.5 – 17.4 | STATISTICAL | Range consistent with UK ambient over logging period. AP mode label: "Evaporator Temp" |
| 40 | System Return Temp | ×0.1 | °C | 16.9 – 52.8 | CONFIRMED | Tracks Shelly return within −0.4°C during stable flow. Actual system return water temp (EWT). AP mode label: "T5 Return Temp" |
| 45 | Discharge Gas Temp | ×0.1 | °C | 17.3 – 84.1 | STATISTICAL | Only register reaching >60°C; r=0.922 vs flow temp; mean 7.6°C above condensing temp. AP mode label: "T10 Discharge" |
| 45 | Discharge Gas Temp | ×0.1 | °C | 17.3 – 84.1 | CONFIRMED | Only register reaching >60°C; r=0.922 vs flow temp; mean 7.6°C above condensing temp. AP mode label: "T10 Discharge" |
| 47 | Flow Rate | ×0.01 | l/min | — | NAMED | Sika VVX20 flow meter built into unit |
| 50 | Reported COP | ×0.01 | — | 2.75 – 5.97 | STATISTICAL | Mean 4.23 consistent with live COP; negative correlation with flow temp confirms higher lift → lower COP. Previously labelled "Suction Pressure" |
| 50 | Suction | ×0.01 | — | 2.75 – 5.97 | CONFIRMED | Cross-checked with HP installer page labelled: "Suction (bar). Previously labelled "Reported COP" |
| 51 | Compressor Speed | ×1 | % | 0 – 100 | STATISTICAL | Exact 0–100 range; correlates with compressor frequency |
| 52 | Fan Suction | ×1 | Pa | - | CONFIRMED | Cross-check with HP installer page labelled: "Fan suction (Pa)" |
| 53 | Compressor Frequency | ×0.1 | Hz | 0 – 60 | STATISTICAL | Raw 0–600 = 0–60 Hz; r=0.708 vs compressor speed % |
| 64 | Heat Output | ×1 (signed Int16) | W | Observed: −8,870 to +6,745 (AdamLC 24h, 13 Apr 2026). Theoretical Int16: ±32,767 | CONFIRMED | r=0.999 vs flow×ΔT thermal calculation (heating, original identified.md analysis). Signed interpretation confirmed by two installations 13 Apr 2026: AdamLC defrost peaks −8,276 W / −8,870 W (raw 57,260 / 56,666); Stu startup transients −4 to −893 W. R48 phases during defrost validate reverse-cycle physics (3.85 bar equalized at entry, ~16 bar at peak-negative R64). |
| 66 | Operating Mode | ×1 | enum | 0 – 3 | STATISTICAL | Discrete values 0/1/2/3 — likely Off / Heating / DHW / Defrost. Requires operational confirmation |
Expand Down
9 changes: 9 additions & 0 deletions qsh-modbus-sniffer/CHANGELOG.md
Original file line number Diff line number Diff line change
@@ -1,5 +1,14 @@
# Changelog

## 4.10.0 - 2026-07-26

### Revise registers based on cross-validation

Updated the following registers based on HP installer page
`Cosy Modbus Reg 52` -> `Fan suction`
`Cosy DHW Cylinder Temp` -> `Discharge Gas Temp`
`Cosy Reported COP` -> `Suction`

## 4.9.0 - 2026-07-26

### Breaking
Expand Down
2 changes: 1 addition & 1 deletion qsh-modbus-sniffer/config.yaml
Original file line number Diff line number Diff line change
@@ -1,6 +1,6 @@
name: "QSH Modbus Sniffer"
description: "Passive Modbus RTU sniffer for Octopus Cosy 6 heat pump. Captures all traffic between hub and outdoor unit via Waveshare RS485-to-WiFi gateway."
version: "4.9.0"
version: "4.10.0"
slug: "qsh_modbus_sniffer"
url: "https://github.com/stuartleeks/qsh-modbus-sniffer"
arch:
Expand Down
23 changes: 9 additions & 14 deletions qsh-modbus-sniffer/rootfs/opt/qsh/cosy6_decoder.py
Original file line number Diff line number Diff line change
Expand Up @@ -160,12 +160,11 @@
# Previously misnamed "Condenser Mid Temp" — regs 29/30 are the actual
# condenser (refrigerant) sensors. This is the water side.
44: {"name": "T9 Flow Temp", "scale": 0.1, "unit": "°C", "icon": "mdi:thermometer-water", "class": "temperature"},
# CONFIRMED: DHW cylinder temp. During active DHW cycle (2026-02-18
# 06:30-08:21), read 52.4°C rising to 54.4°C toward 55°C setpoint.
# Range 22-82°C spans ambient (off) through DHW boost temperatures.
# CONFIRMED: Compressor discharge gas temp. Matches HP installer page.
# Previously misnamed "DHW Cylinder Temp" - not available via Modbus
# Previously misnamed "Compressor Shell Temp" — reg 56 is the actual
# discharge temp (40.8°C), confirming this is NOT a compressor sensor.
45: {"name": "DHW Cylinder Temp", "scale": 0.1, "unit": "°C", "icon": "mdi:thermometer-high", "class": "temperature"},
45: {"name": "Discharge Gas Temp", "scale": 0.1, "unit": "°C", "icon": "mdi:thermometer-high", "class": "temperature"},
# CONFIRMED (defrost validated, R290 cross-check): Primary frost signal.
# Steady state 5.8-7.8°C. Drops to 0°C at defrost trigger.
# Spikes to 37-55°C during hot gas defrost, decays as ice melts.
Expand Down Expand Up @@ -206,16 +205,12 @@
# 13 bar → 35.1°C (matches condenser inlet R29). 5 bar → 4.8°C (matches
# equalized evaporator R55). Closed.
48: {"name": "Discharge Pressure", "scale": 0.01, "unit": "bar", "icon": "mdi:gauge-full", "class": "pressure"},
# STATISTICAL (identified.md + 2026-04-05 analysis): Reported COP.
# Raw range 236-635 at scale ×0.01 = 2.36-6.35 (unitless ratio).
# identified.md: mean 4.23, negative correlation with flow temp (higher
# lift → lower COP). Cross-validated: reg_64/reg_27 implied COP ≈ 3.94,
# Δ = 7% from reg_50 — within measurement uncertainty.
# 2026-04-05: inversely correlated with power/heat output. Mode means:
# idle 52.9 (/100=5.3), heating 35.6 (/100=3.6), DHW 32.0 (/100=3.2).
# Higher COP at idle is physically expected (no lift, residual circulation).
50: {"name": "Reported COP", "scale": 0.01, "unit": "", "icon": "mdi:gauge", "class": None},

# CONFIRMED: Cross-validated with HP installer page during DWH cycle.
# Previously Reported COP but unlikely to be provided via Cosy
50: {"name": "Suction", "scale": 0.01, "unit": "bar", "icon": "mdi:gauge", "class": "pressure"},
# CONFIRMED: Cross-validated with HP installer page during DHW cycle
52: {"name": "Fan Suction", "scale": 1, "unit": "Pa", "icon": "mdi:gauge", "class": "pressure"},

# --- Flow Rate ---
# NAMED: Second sniffer matched to "Flow Rate" from HP installer page.
# Value 1714. Units unclear — if ×0.01 = 17.14 l/min.